Launch line
Pad-mounted distribution transformers
Dead-front, compartmental, liquid-filled units for underground distribution. Single-phase for residential loops; three-phase for commercial, institutional and industrial service.
- IEEE C57.12.00
- IEEE C57.12.34 (three-phase)
- IEEE C57.12.25 / C57.12.26 (single-phase)
- ANSI C57.12.28 (enclosure integrity)
- IEEE C57.12.90 (test code)
- DOE 10 CFR 431 Subpart K
Ratings
| Type | Ratings | Primary | Secondary | BIL | Construction |
|---|---|---|---|---|---|
| Single-phase | 25 to 167 kVA | 7200/12470Y V, 12470GrdY/7200 V, others on request | 120/240 V | 95 kV | Dead-front, loop-feed or radial, mineral oil |
| Three-phase | 75 to 2,500 kVA | 12,470 V delta or 12470Y/7200 V (15 kV class); 24.9 kV class on request | 208Y/120 V or 480Y/277 V | 95 kV (125 kV at 24.9 kV) | Dead-front, loop-feed or radial, bayonet and current-limiting fusing, mineral oil (FR3 on request) |
- Impedance per IEEE C57.12.34 ranges unless the buyer's material standard states otherwise.
- Load-break switches, fusing, pressure-relief devices, tap changers and accessories specified per the buyer's standard drawing.
- Tank finish Munsell 7GY 3.29/1.5 (pad-mount green) unless otherwise specified; ANSI C57.12.28 enclosure integrity for tamper resistance.
What arrives with the quote.
Every quote for this product line includes the documents below, so your engineer can approve before anything is built.
- DOE efficiency certificationCertificate of compliance and DOE database listing for each model offered.
- Per-unit test reportFactory test report per IEEE C57.12.90: ratio, polarity, resistance, no-load and load losses, impedance, applied and induced voltage.
- Guaranteed lossesNo-load and load losses stated per model so the buyer can run its total-ownership-cost evaluation.
- Outline and nameplate drawingsDimensional drawing, weights, fluid volume and nameplate data for approval before manufacture.
- Country-of-origin statementOrigin of the unit and of its core, windings, tank and bushings.
- Warranty termsStated in each quote and administered in the United States.
Send ratings, quantities and a delivery point.
We reply within one business day with price, lead time and the documents above. Attach your material standard if you have one.
Other product lines
Launch line
Pole-mounted distribution transformers
Conventional and CSP single-phase overhead units for feeders, services and rural lines. Standard utility kVA sizes and primary voltages.
Ratings and standards →Phase two
Medium-voltage switchgear
Pad-mounted, air-insulated, dead-front sectionalizing and fused switchgear for underground loops. Quoted against the buyer's one-line and material standard.
Ratings and standards →Larger units
Substation and power transformers
Liquid-filled substation transformers from 2,500 kVA to 30 MVA and power transformers from 10 to 300 MVA, 69 to 345 kV class, including generator step-up units and autotransformers. Quoted with manufacturers that have plants in the United States and Canada, with factory acceptance testing and field service through our service partner.
Ratings and standards →