Larger units
Substation and power transformers
Liquid-filled substation transformers from 2,500 kVA to 30 MVA and power transformers from 10 to 300 MVA, 69 to 345 kV class, including generator step-up units and autotransformers. Quoted with manufacturers that have plants in the United States and Canada, with factory acceptance testing and field service through our service partner.
- IEEE C57.12.00
- IEEE C57.12.10
- IEEE C57.12.90
- IEEE C57.91 (loading)
- IEEE C57.104 (DGA)
- IEEE C57.131 (LTC)
- NEMA TR 1 (sound)
Ratings
| Type | Ratings | High voltage | Low voltage | BIL | Construction |
|---|---|---|---|---|---|
| Substation | 2,500 kVA to 30 MVA | 15 to 46 kV class (12.47 to 34.5 kV) | 2.4 to 34.5 kV | 95 to 250 kV | ONAN / ONAF, DETC, LTC on request, mineral oil or natural ester, skid or pad |
| Power, GSU and autotransformer | 10 to 300 MVA | 69 to 345 kV class | 4.16 to 138 kV | 350 to 1,175 kV | ONAN / ONAF / OFAF, LTC and DETC, bushing CTs, monitoring, conservator or sealed |
| Mobile substation | 5 to 60 MVA | 69 to 230 kV class | 4.16 to 34.5 kV | 350 to 900 kV | Trailer-mounted with switchgear and protection, quoted per project |
- Market lead times for power transformers run 100 to 200 weeks in 2026; we quote delivery dates from the factory slot, not from a catalog.
- DOE 10 CFR 431 does not cover units above 2,500 kVA; losses are guaranteed per unit and evaluated with the buyer's A and B factors.
- Buy American, Build America Buy America and country-of-origin requirements are confirmed with the manufacturer before we quote, and documented in the submittal.
- Field service, commissioning tests, oil processing and dissolved-gas analysis are available through our service partner; transport and rigging are quoted per site.
What arrives with the quote.
Every quote for this product line includes the documents below, so your engineer can approve before anything is built.
- DOE efficiency certificationCertificate of compliance and DOE database listing for each model offered.
- Per-unit test reportFactory test report per IEEE C57.12.90: ratio, polarity, resistance, no-load and load losses, impedance, applied and induced voltage.
- Guaranteed lossesNo-load and load losses stated per model so the buyer can run its total-ownership-cost evaluation.
- Outline and nameplate drawingsDimensional drawing, weights, fluid volume and nameplate data for approval before manufacture.
- Country-of-origin statementOrigin of the unit and of its core, windings, tank and bushings.
- Warranty termsStated in each quote and administered in the United States.
Send ratings, quantities and a delivery point.
We reply within one business day with price, lead time and the documents above. Attach your material standard if you have one.
Other product lines
Launch line
Pad-mounted distribution transformers
Dead-front, compartmental, liquid-filled units for underground distribution. Single-phase for residential loops; three-phase for commercial, institutional and industrial service.
Ratings and standards →Launch line
Pole-mounted distribution transformers
Conventional and CSP single-phase overhead units for feeders, services and rural lines. Standard utility kVA sizes and primary voltages.
Ratings and standards →Phase two
Medium-voltage switchgear
Pad-mounted, air-insulated, dead-front sectionalizing and fused switchgear for underground loops. Quoted against the buyer's one-line and material standard.
Ratings and standards →